The arithmetic behind the work: what to measure, what to type in, and what the answer comes out as. Every formula says what the symbols mean and gives a worked example, so you can check it against a job you have already done.

Quick calculators. A calculator appears where the formula is a single, clean equation with clear symbols. It is a convenience, not an authority: double-check every result yourself, especially doses, loads, torque and safety-critical settings.
RESET

Electrical 12 formulas

Battery bank capacity
Ah = daily Wh x days of autonomy / (V x depth of discharge)
SYMBOLS · DoD = usable fraction
UNITS · Ah
HOW TO USE

Sizing an off-grid battery bank for the days you expect poor weather.

EXAMPLE

3 kWh a day for 2 days at 50% DoD on 24 V needs 500 Ah.

battery bank solar
Battery runtime
t = (Ah x V x efficiency) / load watts
SYMBOLS · Ah = amp-hours; V = volts
UNITS · hours
HOW TO USE

Rough runtime for a battery bank before depth-of-discharge limits.

EXAMPLE

100 Ah at 12 V and 80% efficiency running 100 W lasts about 9.6 h.

battery runtime off-grid
Cable size from current
A = I / current density
SYMBOLS · A = cross-section; current density about 3-5 A/mm2
UNITS · mm2
HOW TO USE

A first check on cable size. Always follow local wiring rules and derating factors.

EXAMPLE

20 A at 4 A/mm2 suggests at least 5 mm2 before derating.

electrical cable current
Capacitive reactance
Xc = 1 / (2 x pi x f x C)
SYMBOLS · f = frequency; C = capacitance
UNITS · ohms
HOW TO USE

How a capacitor resists alternating current. Used in motor starting and filters.

EXAMPLE

10 uF at 50 Hz has 318 ohm reactance.

QUICK CALCULATOR Xc = result
Enter values above.

Convenience only. Double-check the result against the worked example or a second method before you use it.

electrical reactance capacitor
Capacitor energy
E = 0.5 x C x V2
SYMBOLS · C = capacitance in farads; V = voltage
UNITS · joules
HOW TO USE

Stored energy in a capacitor, from motor start cans to smoothing banks.

EXAMPLE

1000 uF at 400 V stores 80 J.

QUICK CALCULATOR E = result
Enter values above.

Convenience only. Double-check the result against the worked example or a second method before you use it.

electrical capacitor energy
Generator size
kVA = watts / (1000 x power factor)
SYMBOLS · Add margin for motor starting
UNITS · kVA
HOW TO USE

Matching a generator to a pump, welder or house load without nuisance trips.

EXAMPLE

4 kW at 0.8 PF needs 5 kVA plus surge margin.

generator power kva
Impedance
Z = sqrt(R2 + (XL - XC)2)
SYMBOLS · R = resistance; X = reactance
UNITS · ohms
HOW TO USE

Total opposition to alternating current in motors, pumps and long cable runs.

EXAMPLE

R 30, XL 40, XC 0 gives Z 50 ohm.

electrical impedance ac
Inverter size
VA = watts / power factor; add startup surge
SYMBOLS · Motor loads can surge 3-5 times
UNITS · VA
HOW TO USE

Choosing an inverter for a shed or house. Size for surge, not just running watts.

EXAMPLE

A 1 kW pump with 3x surge needs at least 3 kVA.

inverter solar off-grid
Power factor
PF = real power / apparent power
SYMBOLS · kW / kVA
UNITS · 0 to 1
HOW TO USE

A low power factor means more current for the same useful work. It matters for pumps and motors.

EXAMPLE

8 kW from 10 kVA is a power factor of 0.8.

electrical power-factor motor
Resistance in parallel
1/R = 1/R1 + 1/R2 + ... + 1/Rn
SYMBOLS · R = resistance
UNITS · ohms
HOW TO USE

Parallel circuits, battery banks and multiple loads on one supply.

EXAMPLE

Two 10 ohm resistors in parallel = 5 ohm.

electrical resistance parallel
Resistance in series
R = R1 + R2 + ... + Rn
SYMBOLS · R = resistance
UNITS · ohms
HOW TO USE

Adding resistors, cable runs or heating elements end to end.

EXAMPLE

10 ohm and 15 ohm in series = 25 ohm.

electrical resistance series
Voltage drop
Vdrop = 2 x I x R x L / 1000
SYMBOLS · I = current; R = resistance per km; L = one-way length
UNITS · volts
HOW TO USE

Sizing cable for a shed, pump or welder so the far end still gets enough volts.

EXAMPLE

10 A over 50 m of 4 mm2 cable drops about 4.4 V.

QUICK CALCULATOR Vdrop = result
Enter values above.

Convenience only. Double-check the result against the worked example or a second method before you use it.

electrical cable voltage
SOURCES & PROVENANCE 1 listed

This page is an AI-organised index. The label means the grouping and cross-links were compiled with AI; the information itself comes from the public-domain books, reports and manuals listed below. Open any source to read the local copy or follow the link to the original publication.

AI-ORGANISED INDEX Runchero formula index Runcheroindex
AI-organised depot index
The index is AI-organised; the linked sources are not.
Formulas collected and indexed with AI. The calculators are convenience tools; double-check every result before using it.